NEC Article 430 — Motor Circuit Sizing

v1.1  ·  Engineering Reference Tool


⚠️ Engineering reference only. Always verify results against the applicable NEC edition, local amendments, and the Authority Having Jurisdiction (AHJ). Not a substitute for a licensed engineer's review.

NEC Article 430 — Motor Circuit Sizing

v1.1
Engineering reference only — verify against applicable NEC edition and AHJ
Project Information
Conductor & System Assumptions
Applies to every circuit (feeder + tap combined)
Defaults
⚠️ Inputs changed — results shown below are out of date.

Point camera at motor nameplate

Snapshot preview

Calculating…

Quick Tour — NEC 430 Motor Circuit Sizer

NEC 430
Motor Circuit Sizer  ·  v1.0
Conductors OCPD Sizing OL Protection Disconnects

Welcome to NEC 430 Motor Circuit Sizer

A free engineering reference for sizing branch-circuit conductors, overcurrent protection, overload devices, and disconnecting means for AC motors — per NEC Article 430. This tour walks through the key features in about 2 minutes. Use ← → arrow keys to navigate.

+ Add Circuit
Circuit 1  —  e.g. MCC-A Panel
HP ——
Voltage ——
Phase ——

Add Motor Circuits

Each circuit is one branch — a motor starter, MCC bucket, or panel circuit. Click + Add Circuit to add as many as the job needs. Give each one a name (e.g. "MCC-A Feeder") for easy reference in the results and PDF.

HP
— Select HP —
Voltage
460V
Phase
3-Phase
FLA — Nameplate Amps  (optional)
​
NEC FLC: 14.0 A  →  conductor min: 17.5 A (125% × FLC per 430.22)

Enter Motor Specifications

Select HP, system voltage, and phase. NEC Table 430.248/250 FLC is looked up automatically. Entering the nameplate FLA gives you more accurate 430.32 overload sizing — leave it blank to size from the NEC table value instead.

OCPD Type
Time-Delay Fuse (TDF)
Max multiplier per NEC 430.52 Table
10 HP / 460V: 14.0 A × 175% = 24.5 A → 25A TDF
175%

Choose Your OCPD Type

Select Time-Delay Fuse, Non-Time-Delay Fuse, Inverse-Time Breaker, or Instantaneous Trip CB. NEC Table 430.52 sets a different maximum multiplier for each type — the tool automatically rounds up to the nearest standard OCPD size.

Circuit 1 — Pump Room
10 HP · 460V 3Ø
5 HP · 460V 3Ø
3 HP · 460V 3Ø
+ Add Motor
Feeder sized per NEC 430.24:
125% × largest + 100% × others

Multiple Motors Per Circuit

Each circuit can hold multiple motors on a shared feeder. Click + Add Motor inside a circuit card to add tap motors. The tool applies NEC 430.24 feeder sizing automatically — 125% of the largest motor FLC plus 100% of all others.

▶ Calculate
✓ Circuit 1 — 10 HP / 460V 3Ø #12 AWG THHN
✓ OCPD: 25A TDF  ·  OL: 17.5A ½" EMT
✓ Disconnect ≥ 16.1A (115% × FLC) 30A disc.

Run Your Calculation

Hit ▶ Calculate to generate the full NEC sizing schedule — conductor AWG & ampacity, conduit size and fill, OCPD rating, overload device, and disconnect for every circuit and motor. Every value is derived from the NEC code sections.

Save
Load
Share Link
Download PDF
✓ Link copied to clipboard!

Save, Share & Export

Save stores your job as a JSON file to resume later. Share Link copies a URL that restores every input — send it to a colleague or bookmark it. Download PDF generates a stamped calculation sheet ready for the job file or permit submittal.